摘要

明清时期“有檩式”古建筑具有构造独特、形态复杂的屋顶结构,对火灾烟气的流动产生显著影响,但现有火灾探测器的布置方案较少考虑这一因素,难以实现有效的早期火灾探测。为加强对明清时期古建筑的火灾防控,该文以硬山顶建筑为例展开研究,采用FDS (fire dynamics simulator)进行火灾数值模拟,分析不同火源位置和不同檩高条件下烟气的蔓延情况,通过设置感烟探测器阵列,进一步探究檩高对各个位置探测器响应特性的影响。研究发现,烟气蔓延过程与探测器响应时序密切相关;火源位于正脊轴线下方,当檩高不超过30 cm时在正脊中心处的探测器最先响应,超过30 cm后在靠近正脊中心两侧的顶棚处布置探测器则可以实现快速响应;火源位于墙角位置,当檩高不超过20 cm时正脊处的探测器均可在60 s之内做出响应。该研究结果可为明清时期同结构类型建筑火灾探测器的合理布置提供技术支撑。

Abstract

Objective: The unique design and complex morphological characteristics of roof structures in the "purlin-type" ancient buildings of the Ming and Qing dynasties significantly influenced the spread of smoke. However, the existing fire detection systems used in ancient structures lack sufficient consideration of the impact of roof architecture on the placement of smoke detectors, which makes it challenging to realize early fire detection effectively and accurately. Therefore, further research on the response time of fire detectors considering purlin height is necessary to strengthen fire prevention and control in ancient buildings. Methods: Through the job-site survey of several gable-roofed buildings in the Forbidden City, the existing smoke detectors were found to be primarily installed on the purlins below the ridge or both sides of the ceiling. However, the scientific basis for these installation positions remains unclear. Thus, this study selected typical gable-roofed buildings with a slope of 27.41° constructed during the Ming and Qing Dynasties as the research object. Fire dynamics simulator was utilized for numerical fire simulation to analyze smoke movement in the different fire source positions (center, edge, and corner) and various purlin heights (low: 10-20 cm; middle: 30-40 cm; high: 50-60 cm). The research further explored the influence of smoke detector response performance on each fire position and purlin height by setting up a 9 × 11 smoke detector array and several slices of smoke mass fraction. In this model, as the purlin height increased, the detectors arranged under them maintained their x and y coordinates, while the z coordinate moved down the corresponding height. The position of the detectors on the ceiling remained unchanged. Results: The findings showed the following: 1) The variation law of the smoke propagation path: In the scenarios of central and edge fires, smoke primarily spread along the horizontal direction of the main ridge. In those of corner fire, when the purlin height was low, the smoke tended to expand upward along the sloping roof; when the purlin height was high, the smoke propagated along the purlin in a "stepped" path. 2) The response time sequence of smoke detectors: For the center and edge fires, the differences in response time of smoke detectors affected by purlin height was approximately 30 s. For the corner fire, when the purlin height was below 20 cm, the detector at the main ridge responded within 60 s, and the variation in the response time of smoke detectors affected by the purlin height can reach up to 45 s. 3) The locations suggested for detector installation: When the purlin height is below 30 cm, the smoke detector should be installed at the center of the main ridge; when the purlin height is above 30 cm, the detectors should be placed on the ceiling near the center of the main ridge on both sides. Conclusions: These findings provide technical support for the rational placement of fire detectors in similar "purlin style" buildings from the Ming and Qing dynasties to achieve comprehensive and timely early detection and warning of fire prevention in ancient buildings.

关键词

硬山顶 / 檩高 / 烟气蔓延 / 感烟探测器 / 响应特性

Key words

gabled roof / purlin height / smoke movement / smoke detectors / response performance

引用本文

导出引用
蒋慧灵, 杨雷音, 周亮. 檩高对明清古建筑感烟探测器响应特性影响研究[J]. 清华大学学报(自然科学版). 2025, 65(4): 634-643 https://doi.org/10.16511/j.cnki.qhdxxb.2024.27.034
Huiling JIANG, Leiyin YANG, Liang ZHOU. Effect of purlin height on the response performance of smoke detectors in ancient buildings of the Ming and Qing dynasties[J]. Journal of Tsinghua University(Science and Technology). 2025, 65(4): 634-643 https://doi.org/10.16511/j.cnki.qhdxxb.2024.27.034
中图分类号: X932   

参考文献

1
WU Y F , CHEN S , WANG D Z , et al. Fire risk assessment of heritage villages: A case study on Chengkan village in China[J]. Fire, 2023, 6 (2): 47.
2
吴儒鸿, 田琼, 郭华, 等. 基于知识图谱的古建筑防火研究热点与发展趋势分析[J]. 湖北工程学院学报, 2023, 43 (6): 123- 128.
WU R H , TIAN Q , GUO H , et al. Analysis of hot spots and development trends of ancient building fire prevention research based on knowledge map[J]. Journal of Hubei Engineering University, 2023, 43 (6): 123- 128.
3
翟羽佳. 教育建筑遗产的消防与可持续保护利用研究——以河南大学近代建筑群为例[D]. 河南: 河南大学, 2022.
ZHAI Y J. Research on fire protection and sustainable conservation and utilization of educational architectural heritage—The example of modern building complex of Henan University[D]. Henan: Henan University, 2022. (in Chinese)
4
ZANG X W , LIU W , WU D L , et al. Contemporary fire safety engineering in timber structures: Challenges and solutions[J]. Fire, 2023, 7 (1): 2.
5
VORWERK P , KELLETER J , MÜLLER S , et al. Classification in early fire detection using multi-sensor nodes—a transfer learning approach[J]. Sensors, 2024, 24 (5): 1428.
6
LI Y, DU H J, WANG B, et al. Research on very early warning aspirating smoke detector deployed in massive guan style buildings from Ming and Qing dynasties in the palace museum[C]//Proceedings of the 5th International Conference on Building Energy and Environment. Singapore: Springer, 2023: 1553-1566.
7
SUN B , ZHANG W S , WANG W , et al. Study on the image processing methods for a flame exposed to an incense smoke environment[J]. Fire, 2023, 6 (7): 270.
8
LIN Q J , ZHANG F Z , JIANG W L , et al. Environmental monitoring of ancient buildings based on a wireless sensor network[J]. Sensors, 2018, 18 (12): 4234.
9
PALMA P , STEIGER R . Structural health monitoring of timber structures-review of available methods and case studies[J]. Construction and Building Materials, 2020, 248, 118528.
10
DAI H , SHI P Z , LIU H B , et al. Electrical fire monitoring IoT framework for ancient architectural complex leveraging edge computing[J]. International Journal of Communication Systems, 2022, 35 (17): e5329.
11
WANG Z M , PENG J N , LIU X Z , et al. Research on grid based fire warning algorithm with YOLOv5s for palace buildings[J]. Emergency Management Science and Technology, 2024, 4, e008.
12
GAO S Y , HUANG G Z , CHEN X L , et al. Two-stage deep learning-based video image recognition of early fires in heritage buildings[J]. Engineering Applications of Artificial Intelligence, 2024, 129, 107598.
13
王茹, 李朴杰, 王亚康, 等. 明清古建筑群火灾智能监测技术研究[J]. 湖南大学学报(自然科学版), 2023, 50 (7): 169- 177.
WANG R , LI P J , WANG Y K , et al. Research on intelligent fire monitoring technology of historic buildings in Ming and Qing dynasties[J]. Journal of Hunan University (Natural Sciences), 2023, 50 (7): 169- 177.
14
刘慧, 李亭, 钟晨. 基于BIM及仿真技术的古建筑火灾防控技术研究[J]. 消防科学与技术, 2023, 42 (9): 1228- 1232.
LIU H , LI T , ZHONG C . Research on ancient building fire prevention and control technology based on BIM and simulation technology[J]. Fire Science and Technology, 2023, 42 (9): 1228- 1232.
15
KHAN A A , ZHANG T H , HUANG X Y , et al. Machine learning driven smart fire safety design of false ceiling and emergency response[J]. Process Safety and Environmental Protection, 2023, 177, 1294- 1306.
16
LIU C X , LIU S T , HUANG P , et al. Experimental study on the temperature distribution of impingement flow in a double slope roof generated by jet fire[J]. Journal of Building Engineering, 2024, 82, 108247.
17
CLEARY T , TAYLOR G . Evaluation of empirical evidence against zone models for smoke detector activation prediction[J]. Fire Technology, 2023, 59 (6): 3129- 3156.
18
ZIGAR D N , BLAGOJEVIĆ M D , PEŠIĆ D J , et al. Smoke detector placement in compartments with honeycomb ceiling: A numerical study[J]. Thermal Science, 2023, 27 (3): 2489- 2500.
19
CHEN N , ZHANG T W , MEI Z B . Experimental study on the response characteristics of photoelectric smoke detectors below grid ceilings of different hollowing rate[J]. Procedia Engineering, 2012, 45, 602- 609.
20
YAN X , GERNAY T . Numerical modeling of localized fire exposures on structures using FDS-FEM and simple models[J]. Engineering Structures, 2021, 246, 112997.
21
中华人民共和国公安部. 火灾自动报警系统设计规范: GB 50116—2013[S]. 北京: 中国计划出版社, 2014.
Ministry of Public Security of the People's Republic of China. Code for design of automatic fire alarm system: GB 50116—2013[S]. Beijing: China Planning Press, 2014. (in Chinese)
22
刘瑾洲, 都海江, 王波, 等. 基于FDS软件的故宫博物院养心殿后殿火灾数值模拟研究[J]. 工业建筑, 2023, 53 (6): 171- 180.
LIU J Z , DU H J , WANG B , et al. Research on numerical simulation of fire in the back hall of Yangxin Hall of the Palace Museum based on FDS[J]. Industrial Construction, 2023, 53 (6): 171- 180.
23
CICIONE A , WALLS R S . Towards a simplified fire dynamic simulator model to analyse fire spread between multiple informal settlement dwellings based on full-scale experiments[J]. Fire and Materials, 2021, 45 (6): 720- 736.
24
HUANG P , LIU S T , LIU C X , et al. Flame extension lengths beneath a double slope roof induced by gaseous fuel jet flame[J]. Fuel, 2023, 350, 128891.
25
ZHANG X L , HU L H , DELICHATSIOS M A , et al. Experimental study and analysis on flame lengths induced by wall-attached fire impinging upon an inclined ceiling[J]. Proceedings of the Combustion Institute, 2019, 37 (3): 3879- 3887.
26
杨一帆. 砖木结构古建筑火灾风险分析与数值模拟研究——以庙宇类建筑为例[D]. 西安: 西安建筑科技大学, 2023.
YANG Y F. Fire risk analysis and numerical simulation of ancient buildings with Brick and Wood Structure—taking temple buildings as an example[D]. Xi'an: Xi'an University of Architecture and Technology, 2023. (in Chinese)

基金

国家重点研发计划项目(2021YFC1523504)
北京市自然科学基金面上项目(8222021)

版权