为揭示城市高压电缆隧道网络化结构对火灾蔓延特性的影响机制, 并为电缆隧道的火灾防控与结构设计提供依据, 该文通过在某城市地下电缆隧道开展全尺寸现场试验, 并利用火灾动力学数值模拟构建了不同隧道结构特性与通风系统耦合的火灾蔓延模型。该文模拟分析了各工况下的电缆隧道火灾过程, 对比分析了模拟数据与试验数据, 并研究不同工况下火灾发生时烟气的扩散行为、 火焰蔓延速度以及温度分布规律。结果表明: 多根多层电缆燃烧条件下, 火源上方顶棚温度迅速升高, 电缆数量增加显著提升了热释放率; 火源左侧的烟气在火灾初期蔓延速度较快, 随着时间推移, 大量外部空气的进入会引起烟气回流, 导致局部温度进一步升高; 多根多层电缆燃烧条件下的CO体积分数显著上升, 说明该条件下燃烧效率低, 产生了更多有毒气体; 在火源垂直上方, 不同风速条件下CO体积分数的变化呈现一定的规律, 在多层电缆条件下, 较高的风速能够改善气体稀释效果, 从而影响CO的生成和扩散。该文揭示了电缆数量、 布置层数与通风系统对隧道火灾危险性的综合影响, 研究结果可为高压电缆隧道的消防设计提供技术支撑。
Abstract
[Objective] To better understand how the structural characteristics of urban high-voltage cable tunnel networks affect fire propagation, this study aimed to provide a scientific basis for fire prevention, control strategies, and tunnel design optimization. Specifically, fire propagation behavior under different structural configurations and ventilation systems in cable tunnels was investigated. Key fire dynamics parameters analyzed included temperature distribution, smoke propagation, flame spread speed, and toxic gas concentrations for both single-layer and multilayer cable arrangements. [Methods] The investigation relied on three-dimensional fire dynamics simulations using Fire Dynamics Simulator software to explore fire propagation in urban high-voltage cable tunnels. Various tunnel structural configurations were analyzed, including single-layer and multilayer cable arrangements, with and without ventilation systems. Critical fire parameters, such as heat release rate (HRR), ceiling temperatures above the fire source, smoke flow patterns, and toxic gas concentrations, were examined under different fire scenarios. Numerical modeling provided detailed insights into how fire dynamics interact with tunnel structural features, emphasizing the significance of cable layout and ventilation. The study also explored how ventilation affects smoke behavior, assessing its influence on fire spread, temperature, and gas emissions. [Results] The results revealed distinct differences in fire behavior depending on tunnel structure and ventilation. Multilayer cable configurations caused ceiling temperatures above the fire source to rise significantly faster and reach higher peaks within 400 s compared to single-layer arrangements. This rapid increase in temperature indicated that the denser cable arrangement boosted the HRR, resulting in greater thermal effects. Smoke propagation was highly dynamic. During the early stages, it initially spread rapidly to one side of the fire source. Ventilation systems, however, altered this behavior by reversing the smoke flow direction over time. This reversal created localized temperature increases and more complex smoke distribution patterns. It also introduced cooler air into the system, influencing flame propagation and heat transfer dynamics. Toxic gas analysis showed that carbon monoxide levels were significantly greater for multilayer cables between 300 s and 500 s, indicating more incomplete combustion and increased hazardous gas emissions in these configurations. Flame propagation was faster, and heat transfer effects were more pronounced in multilayer configurations, highlighting the critical role of structural design in fire dynamics. These results underscore the heightened fire hazards posed by multilayer cable arrangements, including faster flame spread, greater thermal effects, and elevated toxic gas concentrations. [Conclusions] This study emphasizes the critical need for optimizing tunnel designs and ventilation systems to mitigate fire risk effectively in urban high-voltage cable tunnels. Multilayer cable arrangements notably increased heat release rates, toxic gas emissions, and flame propagation intensity, exacerbating fire hazards. While ventilation systems can positively influence smoke propagation and control localized temperatures, improper ventilation strategies may introduce risks, such as smoke flow reversal and uneven heat distribution. These findings provide essential technical insights for developing fire safety measures, highlighting the need for prevention and control strategies tailored to the structural and operational characteristics of urban high-voltage cable tunnels. By addressing these challenges, this research helps improve fire resilience, enhance infrastructure safety, and protect personnel during fire emergencies. This study provides a valuable scientific foundation for improving fire safety management in these tunnels, with practical implications for designing safer infrastructure and implementing effective fire prevention strategies.
关键词
电缆隧道 /
火灾蔓延 /
数值模拟 /
烟气扩散 /
全尺寸试验
Key words
cable /
tunnel fire spread /
numerical simulation /
smoke diffusion /
full-scale experiments
{{custom_sec.title}}
{{custom_sec.title}}
{{custom_sec.content}}
参考文献
[1] NIU Y J, LI W T. Simulation study on value of cable fire in the cable tunnel [J]. Procedia Engineering, 2012, 43: 569-573.
[2] DELICHATSIOS M A. The flow of fire gases under a beamed ceiling [J]. Combustion and Flame, 1981, 43: 1-10.
[3] AMOUZANDEH A, ZEIML M, LACKNER R. Real-scale CFD simulations of fire in single-and double-track railway tunnels of arched and rectangular shape under different ventilation conditions [J]. Engineering Structures, 2014, 77: 193-206.
[4] FAN C G, JIN Z F, ZHANG J Q, et al. Effects of ambient wind on thermal smoke exhaust from a shaft in tunnels with natural ventilation [J]. Applied Thermal Engineering, 2017, 117: 254-262.
[5] KAZEMIPOUR A, AFSHIN H, FARHANIEH B. A comprehensive study on the critical ventilation velocity in tunnels with different geometries [J]. International Journal of Ventilation, 2015, 14(3): 303-320.
[6] TANG F, DENG L, MENG N, et al. Critical longitudinal ventilation velocity for smoke control in a tunnel induced by two nearby fires of various distances: Experiments and a revisited model [J]. Tunnelling and Underground Space Technology, 2020, 105: 103559.
[7] 牛坤, 徐大军, 张晋, 等. 综合管廊电缆火灾的试验和数值模拟研究[J]. 工业安全与环保, 2024, 50(7): 1-5. NIU K, XU D J, ZHANG J, et al. Experimental and numerical simulation study on cable fire in comprehensive pipe gallery [J]. Industrial Safety and Environmental Protection, 2024, 50(7): 1-5. (in Chinese)
[8] URA F, KAWABATA N, TANAKA F. Characteristics of smoke extraction by natural ventilation during a fire in a shallow urban road tunnel with roof openings [J]. Fire Safety Journal, 2014, 67: 96-106.
[9] XU T, CHEN C K, DU W H, et al. Experimental study on fire spread behavior of single 110 kV cable under different layout conditions [J]. Fire Safety Journal, 2023, 141: 103957.
[10] LIANG K, HAO X F, AN W G, et al. Study on cable fire spread and smoke temperature distribution in T-shaped utility tunnel [J]. Case Studies in Thermal Engineering, 2019, 14: 100433.
[11] AN W G, TANG Y H, LIANG K, et al. Study on temperature distribution and CO diffusion induced by cable fire in L-shaped utility tunnel [J]. Sustainable Cities and Society, 2020, 62: 102407.
[12] ZHAO Y C, ZHU G Q, GAO Y J. Experimental study on smoke temperature distribution under different power conditions in utility tunnel [J]. Case Studies in Thermal Engineering, 2018, 12: 69-76.
[13] 李建, 史聪灵, 李昀松, 等. 隧道与横通道交叉角对火灾烟气蔓延影响机制研究[J]. 中国安全生产科学技术, 2020, 16(7): 36-42. LI J, SHI C L, LI Y S, et al. Research on influence mechanism of crossing angle between tunnel and cross passage on fire smoke spread [J]. Journal of Safety Science and Technology, 2020, 16(7): 36-42. (in Chinese)
[14] 苏峰, 张钧, 朱晓平, 等. 基于FDS的管廊电缆火灾动态风险评估研究[J]. 中国安全生产科学技术, 2024, 20(5): 77-83. SU F, ZHANG J, ZHU X P, et al. Research on dynamic risk assessment of cable fire inside utility tunnel based on FDS [J]. Journal of Safety Science and Technology, 2024, 20(5): 77-83. (in Chinese)
[15] 李献晶, 赵恒泽, 李晔. 基于正交试验的隧道火灾影响因素研究[J]. 华北理工大学学报(自然科学版), 2023, 45(1): 126-132. LI X J, ZHAO H Z, LI Y. Study on influencing factors of tunnel fire based on orthogonal test [J]. Journal of North China University of Science and Technology (Natural Science Edition), 2023, 45(1): 126-132. (in Chinese)
[16] 杜进芳, 谢春龙. 美国消防协会NFPA 1851标准2020版分析[C]//中国消防协会. 2022中国消防协会科学技术年会论文集. 中国, 北京: 应急管理出版社, 2022: 5. DU J F, XIE C L. Analysis of the 2020 edition of NFPA 1851 standard of the National Fire Protection Association [C]//China Fire Fighting Association. Annual Scientific and Technical Conference of China Fire Protection Association. Beijing, China: Emergency Management Press, 2022: 5. (in Chinese)
[17] 钟茂华, 刘畅, 杨宇轩, 等. 地铁单面坡隧道列车火灾通风模式研究[J]. 中国安全生产科学技术, 2018, 14(12): 5-13. ZHONG M H, LIU C, YANG Y X, et al. Study on ventilation mode for train fire in metro tunnel with single-side slope [J]. Journal of Safety Science and Technology, 2018, 14(12): 5-13. (in Chinese)
基金
国家自然科学基金项目(52104198);北京市自然科学基金项目(8232014);中国电力科学研究院有限公司研究开发项目(GC83-23-004)