Energy efficiency analysis of phase-change air-assisted liquid cooling systems for high-density data centers

Lu WANG, Xinyi WANG, Bo ZHANG, Xiaoxuan CHEN, Zhen LI

Journal of Tsinghua University(Science and Technology) ›› 2026, Vol. 66 ›› Issue (4) : 810-817.

PDF(7709 KB)
PDF(7709 KB)
Journal of Tsinghua University(Science and Technology) ›› 2026, Vol. 66 ›› Issue (4) : 810-817. DOI: 10.16511/j.cnki.qhdxxb.2025.22.031
Power and Energy

Energy efficiency analysis of phase-change air-assisted liquid cooling systems for high-density data centers

Author information +
History +

Abstract

Objective: With the rapid advancement of artificial intelligence and high-performance computing, data centers are increasingly challenged to achieve effective thermal management and high energy efficiency. Traditional air-cooling methods struggle to handle rising power density, while liquid cooling offers superior heat transfer capabilities but often lacks deployment flexibility. To fully leverage the advantages of air and liquid cooling systems, this study proposes two server-level phase-change air-assisted liquid cooling (AALC) systems to enhance cooling performance, maintain modular deployment, and reduce energy consumption in high-density data centers. Methods: Two technical configurations were investigated: an air-cooling retrofitting scheme (System 1) and a hybrid solution incorporating a heat pipe composite air conditioner (System 2). Both systems utilized a pump-free, gas-liquid phase-change heat transfer loop to enable passive fluid circulation and simplify the structural design. System 1 was designed to combine the structural simplicity and deployment flexibility of air-cooling systems with the high heat transfer efficiency of liquid cooling. It enabled seamless upgradation of high-density cabinets within limited space in existing air-cooled data centers without requiring large-scale infrastructure modifications. An experimental platform simulating a 50kW cabinet heat load was developed using five electric heating modules. The thermal performance of System 1 was evaluated by monitoring the average temperature and surface uniformity across multiple evaporators. To further improve the energy-saving capability and year-round deployment potential across different climatic zones of China, System 2 was developed based on System 1 by incorporating a heat pipe composite air conditioner on the cold source side. This configuration retained the core advantages of passive two-phase cooling while enhancing the effectiveness of natural cooling. For System 2, annual power usage effectiveness (PUE) was simulated using hourly meteorological data from five representative Chinese cities. The total power consumption of the cooling system—including terminal fan power, outdoor fan power, and compressor power—was modeled using empirical polynomial-based expressions. In addition, economic metrics, such as annual energy savings and payback period, were evaluated. Results: System 1 exhibited stable operation under a 50kW cabinet heat load. The average temperature of the two-phase loop reached 39.85 ℃, and the maximum surface temperature difference among five vertical evaporators was only 1.9℃, demonstrating excellent thermal uniformity and heat dissipation capacity. The simulation results of System 2 showed up to 30% energy savings over conventional computer room air handler (CRAH) systems because of the enhanced use of natural cooling. In cities such as Beijing and Xi'an, the annual PUE was reduced to as low as 1.16. The hybrid operation considerably lowered fan and compressor energy consumption. Economic analysis indicated a payback period of approximately 1.89 years, confirming the financial viability of System 2. Conclusions: The proposed AALC systems provide a practical and scalable solution for thermal management in high-density data centers. System 1 verifies the feasibility of passive phase-change cooling for flexible cabinet-level retrofitting.

Key words

data center / air-assisted liquid cooling / phase-change heat transfer / energy efficiency analysis / high power density

Cite this article

Download Citations
Lu WANG , Xinyi WANG , Bo ZHANG , et al . Energy efficiency analysis of phase-change air-assisted liquid cooling systems for high-density data centers[J]. Journal of Tsinghua University(Science and Technology). 2026, 66(4): 810-817 https://doi.org/10.16511/j.cnki.qhdxxb.2025.22.031

References

1
中国制冷学会数据中心冷却工作组. 中国数据中心冷却技术年度发展研究报告2024[R]. 北京: 中国建设科技出版社, 2025.
Working Group on Data Center Cooling. Chinese Association of Refrigeration. Annual development research report on data center cooling technology in China, 2024[R]. Beijing: China Architecture & Building Press, 2025. (in Chinese)
2
中商产业研究院. 2024—2029年中国数据中心建设市场需求预测及发展趋势前瞻报告[R]. 深圳: 中商产业研究院, 2024.
China Business Industry Research Institute. China data center construction market demand forecast and development trend forecast report, 2024-2029[R]. Shenzhen: China Business Industry Research Institute, 2024. (in Chinese)
3
刘迪, 曹军威, 刘明爽. 分布式数据中心信息能量协同优化策略[J]. 清华大学学报(自然科学版), 2022, 62 (12): 1864- 1874.
LIU D , CAO J W , LIU M S . Collaborative optimization strategy of information and energy for distributed data centers[J]. Journal of Tsinghua University (Science & Technology), 2022, 62 (12): 1864- 1874.
4
中国通服数字基建产业研究院. 中国数据中心产业发展白皮书(2023)[R]. 南京: 中国通服数字基建产业研究院, 2024.
China Tongfu Digital Infrastructure Industry Research Institute. White paper on the development of China's data center industry (2023)[R]. Nanjing: Digital Infrastructure Industry Research Institute, 2024. (in Chinese)
5
WANG N B , GUO Y H , HUANG C Q , et al. Advances in direct liquid cooling technology and waste heat recovery for data center: A state-of-the-art review[J]. Journal of Cleaner Production, 2024, 477, 143872.
6
KUZAY M , DOGAN A , YILMAZ S , et al. Retrofitting of an air-cooled data center for energy efficiency[J]. Case Studies in Thermal Engineering, 2022, 36, 102228.
7
SHAHI P , SAINI S , BANSODE P , et al. A comparative study of energy savings in a liquid-cooled server by dynamic control of coolant flow rate at server level[J]. IEEE Transactions on Components, Packaging and Manufacturing Technology, 2021, 11 (4): 616- 624.
8
包云皓, 陈建业, 邵双全. 数据中心高效液冷技术研究现状[J]. 制冷与空调, 2023, 23 (10): 58- 69.
BAO Y H , CHEN J Y , SHAO S Q . Research status of high-efficient liquid cooling technology in data center[J]. Refrigeration and Air-Conditioning, 2023, 23 (10): 58- 69.
9
HUANG Y P , LIU B , XU S J , et al. Experimental study on the immersion liquid cooling performance of high-power data center servers[J]. Energy, 2024, 297, 131195.
10
ALKRUSH A A , SALEM M S , ABDELREHIM O , et al. Data centers cooling: A critical review of techniques, challenges, and energy saving solutions[J]. International Journal of Refrigeration, 2024, 160, 246- 262.
11
中国电信, 深知社. 亚太区智算中心液冷应用现状与技术演进白皮书[R]. 北京: 中国电信, 2024.
China Telecom, Deep Knowledge Live. White paper on the current status and technological evolution of liquid cooling applications in intelligent computing centers in the Asia-Pacific region[R]. Beijing: China Telecom, 2024. (in Chinese)
12
HE W , ZHANG J F , LI H L , et al. Optimal thermal management of server cooling system based cooling tower under different ambient temperatures[J]. Applied Thermal Engineering, 2022, 207, 118176.
13
何智光, 陈殿军, 李震. 数据中心全氟冷却技术的应用效果分析[J]. 制冷, 2022, 41 (1): 8- 12.
HE Z G , CHEN D J , LI Z . Analysis of application effect of perfluorinated cooling technology in data centers[J]. Refrigeration, 2022, 41 (1): 8- 12.
14
王飞, 邵双全, 张海南. 数据中心冷却用动力型热管的实验研究[J]. 制冷学报, 2020, 41 (4): 89- 96.
WANG F , SHAO S Q , ZHANG H N . Experimental study on compressor-driven loop heat pipe for data center cooling[J]. Journal of Refrigeration, 2020, 41 (4): 89- 96.
15
周峰, 王芮敏, 马国远, 等. 高热流液冷服务器相变工质的研究及应用进展[J]. 制冷学报, 2024, 45 (6): 23- 32.
ZHOU F , WANG R M , MA G Y , et al. Research and application progress of phase-change working fluid for high-heat-flux liquid cooling servers[J]. Journal of Refrigeration, 2024, 45 (6): 23- 32.
16
CHEN X X , WANG X Y , WANG L , et al. Multistage data center cooling system for temperature gradation and matching[J]. Applied Energy, 2025, 377, 124592.
17
李衍智, 都家宇, 吴莘馨, 等. 先进核能技术中的热管应用[J]. 清华大学学报(自然科学版), 2023, 63 (8): 1173- 1183.
LI Y Z , DU J Y , WU X X , et al. Heat pipe applications for advanced nuclear energy technology[J]. Journal of Tsinghua University (Science & Technology), 2023, 63 (8): 1173- 1183.
18
KONG R , ZHANG H N , TANG M S , et al. Enhancing data center cooling efficiency and ability: A comprehensive review of direct liquid cooling technologies[J]. Energy, 2024, 308, 132846.
19
何智光. 热管复合冷却系统的协同优化分析及应用[D]. 北京: 清华大学, 2019.
HE Z G. Synergy optimization analysis on combined heat pipe cooling system and its application[D]. Beijing: Tsinghua University, 2019. (in Chinese)
20
CHEN X X , WANG X Y , DING T , et al. Experimental research and energy saving analysis of an integrated data center cooling and waste heat recovery system[J]. Applied Energy, 2023, 352, 121875.

RIGHTS & PERMISSIONS

All rights reserved. Unauthorized reproduction is prohibited.
PDF(7709 KB)

Accesses

Citation

Detail

Sections
Recommended

/