Load simulation of arc fault induced explosion of oil-immersed transformer and anti-explosion balance design

Suwen CHEN, Zechen GUO, Xianmin LI, Guanglei QU, Qiang XIE

Journal of Tsinghua University(Science and Technology) ›› 2026, Vol. 66 ›› Issue (7) : 1329-1338.

PDF(1945 KB)
PDF(1945 KB)
Journal of Tsinghua University(Science and Technology) ›› 2026, Vol. 66 ›› Issue (7) : 1329-1338. DOI: 10.16511/j.cnki.qhdxxb.2026.26.010

Load simulation of arc fault induced explosion of oil-immersed transformer and anti-explosion balance design

Author information +
History +

Abstract

Objective: The arc fault of oil-immersed transformers may result in explosions and corresponding fire accidents, which severely affect the safe operation of the power system. However, arc fault tests cannot be conducted on a large scale due to their high cost, implementation difficulty, and low repeatability. As a result, numerical simulations have become an important research method. Various types of simulation methods are available, and the validity and applicability of their numerical results and underlying physical processes need to be examined. Methods: Taking a 500 kV transformer as an example, this study used LS-DYNA to compare the effectiveness of the TNT equivalent method, instantaneous gas injection method, and uniform gas injection method in terms of spatial and temporal characteristics of arc fault explosion load of oil-immersed transformer. Thereafter, the response characteristics and failure modes of the structure, along with the influence of complex internal structures on the propagation of pressure, were explored. Results: The research results indicated the following: (1) The simulations revealed that the uniform gas injection method could reproduce the process of gas production during arc faults and efficiently reflect the effect of arc fault duration, with the generated peak pressure and pressure gradient closely matching the experimental data. The instantaneous gas injection method and TNT equivalent method yielded higher loads and might overestimate the structural responses. However, they could be employed for examining weak points of transformer structures during explosions because of their simple implementation. The uniform gas injection method was suited for precise response analysis and ultimate pressure limit analysis of transformer structures, which required high accuracy.(2) The arc fault load presented a rapid attenuation characteristic in space and time, which enhanced its local effect on the structure. However, due to the spatial limitations of the transformer structure and the space occupation of internal components, the reflection and superposition of pressure waves prevented the pressure from monotonically attenuating in time and space after reaching its peak. The multi-peak characteristics of the internal explosion pressure waves intensified the impulse within the complex structure.(3) Under the considered conditions, plastic deformation of the structure occurred in the turret structure immediately adjacent to the failure location. Bending deformation arose in the tank wall near the failure area, and substantial stress concentration was observed at the corner of the tank. Under high-energy conditions, the possible failure locations were found in the local area near the arc failure and the stress concentration points at the corners. The overall bending deformation could absorb energy and expand the fluid volume within the structure, which allowed the structure to withstand explosion loads.(4) An anti-explosion balance design concept for transformers was proposed, in which different load models were used for preliminary design, balance design, and pressure-relief design. The three stages corresponded to the static pressure bearing condition, the typical fault condition, and the rare occurrence condition. Conclusions: The uniform gas injection method effectively describes the gas generation process of the arc fault, and the load characteristics agree well with the test results. The arc fault load decays rapidly in time and space. Moreover, the complex pressure propagation path inside the transformer will considerably affect the local load. Based on the load and response characteristics, the stepwise balanced design concept adopting different levels of working conditions can improve the anti-explosion performance and realize economic benefits by simply strengthening the structure.

Key words

oil-immersed transformer / arc fault / numerical simulation / load characteristics / anti-explosion balance design

Cite this article

Download Citations
Suwen CHEN , Zechen GUO , Xianmin LI , et al . Load simulation of arc fault induced explosion of oil-immersed transformer and anti-explosion balance design[J]. Journal of Tsinghua University(Science and Technology). 2026, 66(7): 1329-1338 https://doi.org/10.16511/j.cnki.qhdxxb.2026.26.010

References

1
龚立, 阮仁俊, 陈昊宇, 等. 电力变压器防爆技术与减压措施研究[J]. 变压器, 2012, 49 (4): 43- 47.
GONG L , RUAN R J , CHEN H Y , et al. Research on power transformer explosion-proof technologies and pressure mitigation measures[J]. Transformer, 2012, 49 (4): 43- 47.
2
刘昌, 邵山峰, 廖瑞金, 等. 特高压换流变压器绝缘油老化特性研究[J]. 高电压技术, 2019, 45 (3): 730- 736.
LIU C , SHAO S F , LIAO R J , et al. Study on the aging characteristics of insulation oil of UHVDC converter transformer[J]. High Voltage Engineering, 2019, 45 (3): 730- 736.
3
JONSSON L. Fire and safety aspects on high voltage condenser busings[C]// Transformer Technology Conference. Sydney, Australia: CIGRE, 2008.
4
ABI-SAMRA N , ARTEAGA J , DAROVNY B , et al. Power transformer tank rupture and mitigation—a summary of current state of practice and knowledge by the task force of IEEE power transformer subcommittee[J]. Transactions on Power Delivery, 2009, 24 (4): 1959- 1967.
5
MULLER S, BRADY R, DE BRESSY G, et al. Prevention of transformer tank explosion: Part 1—experimental tests on large transformers[C]// Proceedings of the ASME 2008 Pressure Vessels and Piping Conference. Chicago, USA: ASME, 2008: 357-365.
6
BRADY R, MULLER S, DE BRESSY G, et al. Prevention of transformer tank explosion: Part 2—Development and application of a numerical simulation tool[C]// Proceedings of the ASME 2008 Pressure Vessels and Piping Conference. Chicago, USA: ASME, 2008: 49-58.
7
YAN C G , XU Y , ZHANG P , et al. Investigation of the gas bubble dynamics induced by an electric arc in insulation oil[J]. Plasma Science and Technology, 2022, 24 (4): 21- 28.
8
YAN C G , ZHOU X , XU Y , et al. Experimental study on the gas bubble temperature around an arc under insulation oil[J]. IEEE Transactions on Power Delivery, 2021, 36 (2): 1245- 1248.
9
YAN C G , WEI Y Z , XU C , et al. Experimental verification and electromagnetic-mechanics-acoustic field coupling analysis of transformer pressure relief valve malfunctions due to external short-circuit faults[J]. Transactions on Magnetics, 2019, 55 (6): 8102904.
10
闫晨光, 张保会, 郝治国, 等. 电力变压器油箱内部故障压力特征建模及仿真[J]. 中国电机工程学报, 2014, 34 (1): 179- 185.
YAN C G , ZHANG B H , HAO Z G , et al. Modeling and simulation of pressure characteristics of power transformer tanks' internal faults[J]. Proceedings of the CSEE, 2014, 34 (1): 179- 185.
11
CHEN S W, DU G, XIE Q, et al. A preliminary study on anti-explosion performance of UHV transformer[C]// The 3rd IEEE International Conference on Electrical Materials and Power Equipment. Chongqing, China: IEEE, 2021: 1-4.
12
CHEN S W, GUO Z C, XIE Q, et al. Balance design concept for ultra-high voltage transformer against arc fault explosion and its realization[C]// 2023 International Conference on Power System Technology (PowerCon). Ji'nan, China: IEEE, 2023: 1-8.
13
DASTOUS J B, FOATA M. Analysis of faults in distribution transformers with MSC/PISCES-2DELK[C]// MSC World Users' Conference. Los Angeles, USA: MSC World Users' Conference, 1991.
14
DASTOUS J B , LANTEIGNE J , FOATA M . Numerical method for the investigation of fault containment and tank rupture of power transformers[J]. Transactions on Power Delivery, 2010, 25 (3): 1657- 1665.
15
赵志刚, 徐征宇, 王健一, 等. 大型电力变压器火灾安全研究[J]. 高电压技术, 2015, 41 (10): 3378- 3384.
ZHAO Z G , XU Z Y , WANG J Y , et al. Research on the fire safety of large power transformer[J]. High Voltage Engineering, 2015, 41 (10): 3378- 3384.
16
李文贺. 舰船水下爆炸冲击波载荷作用下动力响应研究[D]. 大连: 大连理工大学, 2009.
LI W H. Study on dynamic response of ship structure under underwater explosive impact loading[D]. Dalian: Dalian University of Technology, 2009. (in Chinese)
17
TRENCHAM H . Circuit breaking: Researches by the British electrical and allied industries research association[M]. London: Butterworths Scientific Publications, 1953.
18
ABRAMOWICZ W , JONES N . Dynamic progressive buckling of circular and square tubes[J]. International Journal of Impact Engineering, 1986, 4 (4): 243- 270.
19
BRODEUR S , DASTOUS J B . Design and testing of an arc resistant power transformer tank[J]. IEEE Transactions on Power Delivery, 2020, 35 (2): 699- 706.

RIGHTS & PERMISSIONS

All rights reserved. Unauthorized reproduction is prohibited.
PDF(1945 KB)

Accesses

Citation

Detail

Sections
Recommended

/