Characteristics and heat transfer mechanism of low-voltage AC series arc faults under coupled ambient temperature and wind speed

Qing DENG, Yanchao YE, Wentao DAI, Yingsong LI, Huiling JIANG

Journal of Tsinghua University(Science and Technology) ›› 2026, Vol. 66 ›› Issue (9) : 1795-1804.

PDF(2499 KB)
PDF(2499 KB)
Journal of Tsinghua University(Science and Technology) ›› 2026, Vol. 66 ›› Issue (9) : 1795-1804. DOI: 10.16511/j.cnki.qhdxxb.2026.27.042
Public Safety

Characteristics and heat transfer mechanism of low-voltage AC series arc faults under coupled ambient temperature and wind speed

Author information +
History +

Abstract

Objective: Electrical fires occur frequently in complex environments, where environmental factors such as ambient temperature and wind speed contribute to fire occurrence and spread by changing the behavior of series arc faults. This study investigates the patterns of low-voltage AC series arc faults under the combined effects of ambient temperature and wind speed, with a focus on temperature field evolution, spatial heat transfer, current and voltage responses, and arc energy. Methods: A two-dimensional axisymmetric magnetohydrodynamic model is developed in COMSOL Multiphysics to simulate the thermal-fluid-electromagnetic coupling behavior of an AC series arc fault. This model integrates magnetic and electric fields, heat transfer, laminar flow, and an external circuit. The simulation domain consists of a copper electrode, a graphite electrode, a 3 mm arc gap, an ignition heat source, and the surrounding air. The circuit comprises a 5 Ω resistor and a 220 V/50 Hz AC source. Arc formation is initiated by setting the ignition heat source to 12,000 K. A two-dimensional orthogonal combined design is adopted, including three ambient temperatures (288.15, 298.15, and 308.15 K) and three wind speeds (0, 2, and 4 m·s−1). Average temperature, temperature integral, the root mean square (RMS) of current and voltage, and arc energy are selected as evaluation indicators. Observation points, arranged from the arc center to the outer region, are used to quantify spatial variations in the thermal response. Results: The results show that the arc temperature field expands and contracts with the power-frequency cycle, and this behavior is closely associated with voltage variations. In the absence of wind, the temperature field exhibits a spindle-like shape, with heat accumulating around the arc. At a wind speed of 2 m·s−1, the temperature field shifts in the direction of airflow, and the high-temperature region moves toward the graphite electrode. The effects of wind speed on the temperature field demonstrate clear spatial dependence. In the arc core region, temperature slightly increases with rising wind speed due to thermal contraction concentrating energy near the arc column. In the peripheral region, however, convective cooling dominates. At 4 m·s−1, the average temperature in the outer region decreases by more than 12.06%, and the temperature integral at wind-cooling-dominated observation points decreases by up to 42.27%. The current RMS remains stable between 34.4 and 34.7 A. The voltage RMS is more sensitive to wind speed than ambient temperature, decreasing by approximately 2.55 V when wind speed increases to 4 m·s−1. The arc energy remains stable at 2 m·s−1 and decreases slightly at 4 m·s−1. Ambient temperature has a limited effect on arc energy, exerting only a weak influence under strong wind conditions. Conclusions: Wind speed is the primary environmental factor controlling the temperature field and electrical response of low-voltage AC series arc faults, whereas ambient temperature has a limited effect. Wind enhances heat concentration in the arc core while increasing cooling in the outer region. The current conduction channel remains stable, but voltage and arc energy respond more distinctly to airflow disturbance. These findings provide a theoretical basis for early warning and prevention systems for electrical fires in complex environments.

Key words

arc fault / temperature field / ambient temperature / wind speed / current and voltage

Cite this article

Download Citations
Qing DENG , Yanchao YE , Wentao DAI , et al . Characteristics and heat transfer mechanism of low-voltage AC series arc faults under coupled ambient temperature and wind speed[J]. Journal of Tsinghua University(Science and Technology). 2026, 66(9): 1795-1804 https://doi.org/10.16511/j.cnki.qhdxxb.2026.27.042

References

1
国家消防救援局. 国家消防救援局举行例行新闻发布会[EB/OL]. (2025–01–24)[2026–05–20]. https://js.119.gov.cn/202501/jsxfww-menu-zxft-zxftlb_c_a9f51911e874498586b7.html.
National Fire and Rescue Administration. National Fire and Rescue Administration holds a regular press conference[EB/OL]. (2025–01–24)[2026–05–20]. https://js.119.gov.cn/202501/jsxfww-menu-zxft-zxftlb_c_a9f51911e874498586b7.html. (in Chinese)
2
国家消防救援局. 国家消防救援局举行例行新闻发布会[EB/OL]. (2026–03–17)[2026–05–20]. https://js.119.gov.cn/202603/jsxfww-menu-zxft-zxftlb_c_4093535d4c52493d9e46ec54cc9cbbec.html.
National Fire and Rescue Administration. National Fire and Rescue Administration holds a regular press conference[EB/OL]. (2026–03–17)[2026–05–20]. https://js.119.gov.cn/202603/jsxfww-menu-zxft-zxftlb_c_4093535d4c52493d9e46ec54cc9cbbec.html. (in Chinese)
3
LE V, YAO X, MILLER C, et al. Series DC arc fault detection based on ensemble machine learning[J]. IEEE Transactions on Power Electronics, 2020, 35(8): 7826- 7839.
4
LI C Y, YANG Z H, YAO W B, et al. Experimental study of ignition process caused by poor electrical contact of connecter[J]. Process Safety and Environmental Protection, 2024, 189, 1517- 1526.
5
叶艳超, 蒋慧灵, 邓青. 交流串联故障电弧对低压配电系统上下级电气特性的影响研究[J]. 消防科学与技术, 2025, 44(10): 1471- 1478.
YE Y C, JIANG H L, DENG Q. Research on the impact of AC series fault arcs on the electrical characteristics of upper and lower stages in low-voltage distribution systems[J]. Fire Science and Technology, 2025, 44(10): 1471- 1478.
6
GE F L, QIU T T, ZHANG M S, et al. Experimental research on the thermal characteristic of low-voltage alternating current (AC) arc faults[J]. Fire Safety Journal, 2023, 136, 103732.
7
蒋慧灵, 白嘎力, 周郑, 等. 基于一维空洞卷积神经网络的故障电弧检测方法[J]. 清华大学学报(自然科学版), 2024, 64(3): 492- 501.
JIANG H L, BAI G L, ZHOU Z, et al. An arc fault detection method based on a one-dimensional dilated convolutional neural network[J]. Journal of Tsinghua University (Science and Technology), 2024, 64(3): 492- 501.
8
TSILINGIRIS P T. Thermophysical and transport properties of humid air at temperature range between 0 and 100 ℃[J]. Energy Conversion and Management, 2008, 49(5): 1098- 1110.
9
DU J H, TU R, ZENG Y, et al. An experimental study on the thermal characteristics and heating effect of arc-fault from Cu core in residential electrical wiring fires[J]. PLoS One, 2017, 12(8): e0182811.
10
邓青, 李滢松, 叶艳超, 等. 温湿度对交流串联故障电弧特性和能量释放影响的实验研究[J]. 清华大学学报(自然科学版), 2026, 66(2): 223- 232.
DENG Q, LI Y S, YE Y C, et al. Experimental study on the effects of temperature and humidity on the characteristics and energy release of alternating current series fault arcs[J]. Journal of Tsinghua University (Science and Technology), 2026, 66(2): 223- 232.
11
CABELLO J R, BULLEJOS D, RODRíGUEZ-PRIETO A. Effect of irradiance and temperature on the occurrence of arc flash in photovoltaic power systems[J]. Electric Power Systems Research, 2025, 240, 111224.
12
XU Z L, GAO G Q, WEI W F, et al. Characteristics of pantograph-catenary arc under low air pressure and strong airflow[J]. High Voltage, 2022, 7(2): 369- 381.
13
JIANG C S H, BI M Q, ZHANG S Y, et al. Study on arc characteristics and combustion feature of tree-wire discharge fault in distribution line[J]. Electric Power Systems Research, 2024, 230, 110210.
14
LI Y, XU J Y, WANG P, et al. Research on arc extinguishing characteristics of single-phase grounding fault in distribution network[J]. Energies, 2025, 18(2): 256.
15
WANG L J, ZHANG Z F, CHEN J L, et al. 3D transient MHD simulation of DC breaking vacuum arc based on artificial current zero[J]. Journal of Applied Physics, 2022, 132(6): 063301.
16
WANG L J, LUO M, DENG J, et al. Numerical simulation of multispecies vacuum arc subjected to actual spatial magnetic fields[J]. IEEE Transactions on Plasma Science, 2021, 49(11): 3652- 3662.
17
LI Y, ZHANG R C, YANG K, et al. Numerical investigations of AC arcs' thermal characteristics in the short gap of copper-cored wires[J]. Scientific Reports, 2024, 14(1): 4227.
18
吴祺嵘, 徐婧涵, 张国钢, 等. 基于真型试验和磁流体仿真的电缆单相接地故障电弧场路耦合模型研究[J]. 电力系统保护与控制, 2026, 54(4): 25- 37.
WU Q R, XU J H, ZHANG G G, et al. Arc field-circuit coupling modelling of cable single-phase-to-ground faults based on full-scale tests and magnetohydrodynamic simulations[J]. Power System Protection and Control, 2026, 54(4): 25- 37.
19
ZHANG Z Y, NIE Y M, LEE W J. Approach of voltage characteristics modeling for medium-low-voltage arc fault in short gaps[J]. IEEE Transactions on Industry Applications, 2019, 55(3): 2281- 2289.
20
OKUMA T, MARUYAMA H, HASHIZUME T, et al. Effects of the driving frequency on temperature in a multiphase AC arc[J]. IEEE Transactions on Plasma Science, 2019, 47(1): 32- 38.
21
BOGARRA S, MORENO-EGUILAZ M, ORTEGA-REDONDO JA, et al. A dataset of voltage and current waveforms in an electric arc under low pressure for aircraft power systems[J]. Scientific Data, 2024, 11(1): 1396.
22
WANG Y K, ZHANG F, ZHANG X H, et al. Series AC arc fault detection method based on hybrid time and frequency analysis and fully connected neural network[J]. IEEE Transactions on Industrial Informatics, 2019, 15(12): 6210- 6219.
23
高洪鑫, 王坤远, 王智勇, 等. 三相变频器回路串联故障电弧检测方法研究[J]. 电子测量与仪器学报, 2025, 39(1): 203- 215.
GAO H X, WANG K Y, WANG Z Y, et al. Research on series arc fault detection method in three-phase frequency converter circuit[J]. Journal of Electronic Measurement and Instrumentation, 2025, 39(1): 203- 215.
24
International Organization for Standardization. Explosive atmospheres-Part 20–2: Material characteristics-combustible dusts test methods: ISO/IEC 80079–20–2: 2016[S]. Geneva: International Organization for Standardization, 2016.
25
DU Y, LI G Q. A new temperature-time curve for fire-resistance analysis of structures[J]. Fire Safety Journal, 2012, 54, 113- 120.
26
ZHANG J M, LU C R, GUAN Y G, et al. Thermodynamic properties and transport coefficients of air thermal plasmas mixed with ablated vapors of Cu and polytetrafluoroethylene[J]. Physics of Plasmas, 2015, 22(10): 103518.
27
BABRAUSKAS V. Electric arc explosions-a review[J]. Fire Safety Journal, 2017, 89, 7- 15.
28
朱亮, 张仁军, 田玉吉. 旋转陶瓷片约束TIG电弧形态分析[J]. 焊接学报, 2007, 28(11): 1- 4.
ZHU L, ZHANG R J, TIAN Y J. TIG arc constricted by rotating ceramic plates[J]. Transactions of the China Welding Institution, 2007, 28(11): 1- 4.
29
杨文斌, 齐新华, 车庆丰, 等. 基于辐射光谱的电弧加热器流场焓值测量及效率评估[J]. 光谱学与光谱分析, 2025, 45(S1): 319- 325.
YANG W B, QI X H, CHE Q F, et al. Flowfield enthalpy measurement and efficiency evaluation of arc heater using optical emission spectroscopy[J]. Spectroscopy and Spectral Analysis, 2025, 45(S1): 319- 325.
30
MURPHY A B. Thermal plasmas in gas mixtures[J]. Journal of Physics D: Applied Physics, 2001, 34(20): R151- R173.

RIGHTS & PERMISSIONS

All rights reserved. Unauthorized reproduction is prohibited.
PDF(2499 KB)

Accesses

Citation

Detail

Sections
Recommended

/